亚洲又黄又大又爽毛片_欧美一级精品免费_波多野结衣大战黑人_欧洲另类综合_亚洲日本国产_欧美性视频在线激情_久久免费人成看片中文_日本强奸视频一区二区_国产三级免费观看_日本在线观看一区不卡

Welcome to visit Baoding Zhuoyue Electric Co.,LTD.!
switch 中文  |   switch English
Hotline:
+86-312-3136236/3021783
Your location:Home > Product > Comprehensive
Comprehensive

Three phase capacitance inductance tester

Add time:2022-04-13   Number of views:393  

Summary of instrument

Reactive power compensation capacitor is an important equipment to satisfy reactive power balance in power system. In recent years, the problem of reactive power has been paid more and more attention by the electric industry. Power supply requires real-time balance between active power and reactive power. Therefore, reactive power compensation device should meet the requirements of automatic tracking and real-time compensation, so it is inevitable to frequently cast and cut reactive power compensation capacitor banks. The switching and switching operation of the capacitor bank will produce overcurrent and overvoltage impact, causing damage to the capacitor.

In order to ensure the reliability of the equipment, it is necessary to detect the capacitor defects early and avoid the expansion of the fault regularly. And capacitor are group in parallel on the spot, the traditional method is to remove the bus-bar capacitance, and then use the old capacitance meter measuring, because the capacitor group is composed of tens to hundreds of small capacitors, take out stitches to measure the capacitance of a lot of work, take out stitches and often makes the sliding teeth or not to tighten the screw and leave a safe hidden trouble, also can cause secondary damage capacitance. Therefore, it is very expected that a test instrument can measure the capacitance of each small capacitor without removing wires, reduce the burden of maintenance personnel, improve the efficiency of maintenance work, and improve the safety of distribution network operation.

Three-phase inductance capacitance tester can not remove the state, the measurement of the single phase or various combinations of group parallel capacitor connection type three-phase capacitor, at the same time also can measure all kinds of reactor inductance, the instrument can also measure the condition of power frequency current, the instrument connection is convenient, simple operation, reduce the maintenance staff work, It greatly improves the test efficiency and provides security for the normal operation of power grid.


Technical parameters

1, output voltage: ~ 2V, ~ 15V

2, measuring range: capacitance: 0.01UF ~ 2000uF

                                 Inductance: 1mH ~ 10H

                                 Current: 50mA ~ 10A

                                 Voltage: 0 ~ 25V

3, measuring accuracy: capacitance: ±(1%+2 words)

                                      Inductance: ±(1%+5 words)

                                      Current: ±(1%+2 words)

                                      Voltage: ±(1%+2 words)

4, working power supply: AC220V±10%

5, power frequency: 50±1Hz

6, the instrument power: 150W

7, ambient temperature: -10℃ ~ 50℃

8, environmental humidity: ≤85%RH

9, instrument weight: 3kg

10, overall size: 320mm×240mm×130mm


Home Tel Product