A, use
This type of current transformer is an indoor device, used for current, energy, electricity and measurement in ac lines with frequency of 50-60Hz, 0.66kV and below.
Second, the structure of
This type of current transformer is bus type with annular iron core. The quadratic line is evenly distributed on the core; The insulation is made of resin casting insulation and formed by casting once.
Three, main technical indicators
The secondary current of the current transformer is 5A
Primary current: 10, 15, 20, 25, 30, 40, 50, 60, 80,
100, 150, 200, 300, 400, 500, 600,
800, 1000, 1200, 1500, 2000A
Power frequency withstand voltage: primary to secondary and ground: 3kV / 1 minute
Secondary ground: 3kV / 1 minute
Resistance: primary to secondary and ground: 1000M ω
Secondary ground: 500 M ω
Operating environment: Altitude: not more than 1000 meters
Temperature: - 25 + 40 ℃
Relative humidity: less than 90%