A list,
Z Y DY-900 live cable identification instrument is designed for power cable engineers and cable workers to solve the technical problems of cable identification. Users can accurately identify one target cable from multiple cables through the instrument to avoid serious accidents caused by missawing live cables. Cable identification starts with operations at both ends of the cable. Ensure that the double numbers at both ends of the cable are accurate. The instrument design uses P SK technology, combined with precise algorithm. This product has the functions of live cable identification, power failure cable identification, AC current test, AC voltage test at the same time. It is composed of a transmitter, a transmitting current clamp, a receiver, a receiving flexible current clamp, etc. When identifying live cable, it can pre-calibrate 10 cables at the transmitting end, and then receive and identify at the remote end.
Two, technical indicators
1. Transmitter specifications
Function | Transmit compound pulse frequency current signal, display residual battery voltage, and dynamically indicate emission state |
11.1 V large capacity rechargeable lithium battery, fully charged and continuously working for about 8 hours | |
Output mode | Calipers are coupled when live recognition; Direct output during power outage identification |
625Hz, 1562Hz, 2500Hz and 10KHz (when live identification), press the up and down arrow keys to adjust the emission frequency | |
Pulse voltage | 500V (when power outage is identified) |
Max. 5A (depending on loop resistance) | |
Pulse frequency | 1 times/second |
2ms | |
Storage condition | -20 ℃ ~ 50 ℃, ≤ 95% RH, no condensation |
Operating temperature | -10 ℃ ~ 40 ℃ |
-20 ℃ ~ 50 ℃, ≤ 95% RH, no condensation | |
Compression resistance | The transmitter adopts an integrated special toolbox design, and the box can bear about 200kg pressure |
AC 3700V/rms (before top and bottom of instrument box) | |
Electromagnetic characteristics | IEC 61326 (EMC) Reference Safety Code IEC 61010-1 (CAT III 300V, CAT IV 150V, Contamination Level 2) |
2. Receiver specifications
Function | Live cable identification and power failure cable identification; Measurement of AC voltage, current and frequency |
Power supply | 7.4 V large capacity rechargeable lithium battery, USB charging interface, fully charged and continuously working for about 6 hours |
Receiving frequency | 625Hz, 1562Hz, 2500Hz, 10KHz (when live identification, press the left and right arrow keys to adjust the receiving frequency) |
Gain intensity | 1dB, 10dB, 20dB Press the left and right arrow keys to adjust the gain intensity |
Rated current | Approximately 300mA max |
Detection range | Power failure identification: the coil can detect pulse signals with loop resistance of 0 Ω ~ 8 k Ω; When the detection loop resistance is 8 k Ω, it is necessary to ensure that the transmitter battery power is above 11V (generally, it can reach the cable length of 0-20km, which is mainly determined by the grounding resistance and cable resistance). Live identification: the coil can detect pulse signals with loop resistance of 0 Ω ~ 200 Ω; When the resistance of the detection loop is 200 Ω, it is necessary to ensure that the battery power of the transmitter is above 11V (generally, the cable length can reach 0-6 km, which is mainly determined by the grounding resistance and cable resistance) |
Measuring range | AC voltage: 0.00 V ~ 600V (50Hz/60Hz) |
AC current: 0.00 A ~ 5000A (50Hz/60Hz) | |
Current frequency: 45Hz ~ 70Hz | |
Precision | AC voltage: ± 2% ± 3dgt |
AC current: ± 2% ± 3dgt | |
Current frequency: ± 2Hz | |
Working temperature and humidity | -10 ℃ ~ 40 ℃; Below 80% Rh |
Storage temperature and humidity | -10 ℃ ~ 50 ℃, ≤ 95% RH, no condensation |
Withstand voltage | AC2000V/RMS (in front of the front and rear ends of the housing) |
Suitable safety regulations | IEC61010-1 CAT ⅲ 600V, IEC61010-031, IEC61326, pollution level 2 |