Overview,
ZY6000 fully intelligent wireless high and low voltage nuclear phase meter is composed of wireless receiver, detector, telescopic insulating rod, etc. The receiver adopts 3.5-inch true color LCD screen, which displays the nuclear phase results, phase, frequency and vector diagram indication on the same screen. There are voice prompts such as "X signal normal, Y signal normal, in-phase and out of phase", which are clear and intuitive. The distance of the nuclear phase on the open ground can be up to 160m, and it can fully intelligent the nuclear phase of the voltage line from 1V to 550kV. The bare wire of 35kV and below can directly contact the nuclear phase, and the bare wire of 35kV and above adopts non-contact nuclear phase. The non-contact nuclear phase is to gradually close the detector to the measured wire. When the electric field signal can be induced to complete the nuclear phase, so there is no need to directly contact the high voltage wire, the nuclear phase instrument has the functions of high voltage electroscope, high voltage phase meter, high voltage phase sequence table, can be used for electric inspection, phase sequence test, transformer group judgment, etc..
Technical specifications
Function | Phase, frequency, phase, phase sequence and electrical test of high and low voltage wireless voice core |
Power supply | Receiver: DC 7.4 V Rechargeable Lithium Battery Detector: DC 3.7 V Rechargeable Lithium Battery USB Charging Interface, Working continuously for about 10 hours |
Transmission mode | 315MHz, 433MHz wireless transmission |
Nuclear phase distance | Maximum about 160m |
Measuring range | Nuclear phase voltage level: AC 1V ~ 550kV Phase: 0.0 ° ~ 360.0 ° Frequency: 45Hz ~ 75Hz |
Resolution | 0.1 °; 0.1 Hz |
Nuclear phase mode | Contact nuclear phase: Bare conductors below 35kV or conductors below 110kV with safety insulation skin directly contact nuclear phase. Non-contact core phase (operating with insulated rod): Bare conductor above 35kV, or line above 110kV adopts non-contact core phase, and gradually approaches the conductor. (Operated with insulating rod) |
Rated current | Detector: 35mA max; Receiver: 300mA max |
Insulation strength | Insulated rod: AC 110kV/rms (between the two ends after the insulated rod is fully stretched) Detector: 2000V/rms (between the two ends of the housing) Receiver: 2000V/rms (between the two ends of the housing) |
Suitable safety regulations | The requirements of GB13398-92, GB311.1-311.6-8, 3DL408-91 and the newly issued national power industry standard "General technical conditions for 1kV ~ 35kV portable nuclear phase devices for live working DL/T971-2005" meet IEC61481-A2: 2004; IEC 61243-1 ed.2: 2003 standard |