亚洲又黄又大又爽毛片_欧美一级精品免费_波多野结衣大战黑人_欧洲另类综合_亚洲日本国产_欧美性视频在线激情_久久免费人成看片中文_日本强奸视频一区二区_国产三级免费观看_日本在线观看一区不卡

Welcome to visit Baoding Zhuoyue Electric Co.,LTD.!
switch 中文  |   switch English
Hotline:
+86-312-3136236/3021783
Your location:Home > Product > The marketing class
The marketing class

Zy-a038 Three-phase handheld electrical inspection instrument (Grade 0.5)

Add time:2022-04-18   Number of views:415  

An overview,

The two-way station branch identification instrument produced by our company is a high-precision testing instrument that integrates the functions of station user identification, line branch identification, electrical independence testing between stations, basic electrical parameters testing, voltage and current harmonic content measurement and so on. The instrument adopts the current industry advanced technology and special zero frequency carrier pulse current emission and detection technology, can effectively guarantee the measuring radius is enough to cover all kinds of power supply area users accurate identification of the distance, there is no more than one variable short of high-pressure situations crosstalk, power carrier transmission distance close, affected by the load is large, a total of cable interference, etc.; The recognition success rate can reach 100 percent.

Two, technical indicators

1. Test section of the platform area

Communication mode: special load signal transmission, distance: ≥5km

Current test distance: ≥5km

Identification period: ≤6 seconds

Test success rate: 100%

Number of branch identification: 3 channels for a single host (18 channels can be extended in multi-host mode)

Clamp type current transformer: 750A/1500A flexible current transformer

50mm calipers (50A/100A/250A/500A) (optional)

2. Measurement of electrical parameters

Voltage: ±0.2% Current: ±0.5%

Power: ±0.5% Frequency: ±0.02Hz

Phase: + / - 0.2 °

3. Power quality

Voltage harmonic measurement times: 2-51

Current harmonic measurement times: 2-51

Measurement error of harmonic voltage content: ≤ 0.1%

Measurement error of harmonic current content: ≤ 0.2%

4. Work environment

Working environment temperature: -30℃~60℃

Working environment humidity: ≤95%RH

Working voltage: AC220V±10%

5, insulation

(1) The insulation resistance of voltage and current input terminal to the casing is more than 100M ω.

(2) The input end of the working power supply is subjected to power frequency 1.5kV (effective value) between the shell, and the experiment lasts for 1 minute.

6, weight,

Weight: 1 kg

7, single machine volume

Size: 25 cm * 16 cm * 6 cm


Home Tel Product