An overview,
The reliable and effective connection between grounding downlink and ground network is the fundamental guarantee of equipment operation. Therefore, in "Twenty-five Key Requirements for Preventing major Accidents in electric power production", the conduction detection of grounding device lead down line is clearly proposed. The company developed and produced a series of grounding lead down the conduction tester using 32-bit ARM kernel as the processing core, the whole machine control, automatic self-calibration, steady flow judgment, data processing, resistance display and other functions, the instrument can directly use the internal battery work, greatly facilitate the use of field staff.
Two, technical indicators
1, output current and range: output current: 0-10A, range 0.5MW-300W.
current | range | current | range |
10A | 0.5mW-600mW | 0.5A | 1W-12W |
5A | 1mW-1.2W | 0.2A | 3W-30W |
2A | 10mW-3W | 20mA | 25W-300W |
Note: please use the automatic test function beyond the above range.
2, the test accuracy :0.2% highest resolution: 0.1MW.
3, the instrument uses 65K true color LIQUID crystal display, Chinese menu prompt, easy to operate.
4, with large capacity storage function, can store 2000 test records,
5, working power supply: AC220V±10%, or internal battery.
6, working temperature: -10℃ ~ 40℃.
7, working humidity: environmental humidity < 80%RH.
8. Weight of the instrument: 3㎏.